I was working with RIck Carillo on this previously. Please correct the Heating Hot Water loop PM's to reflect the actual process req
uired to maintain loop water quality in optimal range which would include testing for Nitrites in the parts per million preferably b
etween 600 and 1,200 ppm and recording pH level of the loop. Additionally please add a step for testing discharge pH from the pH neu
tralizing tank (1) that the condensing boilers share and a final step for agitating the media that conditions the condensate pH, one
per neutralizing tank.
Area
SSF UTILITIES-HVAC SYS
|